bvandeusenandClaude Opus 5.5 f035a3b14a fix(snmp): a UPS on mains reads "On battery: No, on mains", not "0s" (#5214)
UPS-MIB upsSecondsOnBattery is zero whenever the UPS is on mains power, so
"On battery for 0s" read as a timer that had just started. The reading gets
its own unit, battery_seconds: zero says "No, on mains", anything else
"for <span>". The metric key stays on_battery_for, so stored history keeps.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
2026-10-08 13:16:24 -04:00

218 lines
9.4 KiB
Python

# plugins/snmp/readings.py
"""What an SNMP device is asked for, and how each answer reads.
A device's readings come from the presets ticked on its form plus any custom
lines. Each reading has a key (the metric name it is stored and alerted on),
a name a person reads, and a unit. A counter (an interface's byte count, any
"total so far") is stored as a rate: the poller turns two samples into a
per-second figure, so a chart and an alert see traffic, not a lifetime total.
"""
from __future__ import annotations
import re
from dataclasses import dataclass
from steward.core.formatting import human_bytes, human_duration
@dataclass(frozen=True)
class Reading:
oid: str
key: str
name: str
unit: str = "number"
scale: float = 1.0
offset: float = 0.0
@property
def counter(self) -> bool:
return self.unit in COUNTER_UNITS
# A counter's unit names what it counts; it is stored as the rate unit it maps
# to, multiplied by the factor (a byte counter is stored as bits per second).
COUNTER_UNITS = {"octets": ("bits_per_second", 8.0), "count": ("per_second", 1.0)}
STATUS_WORDS = {
"if_status": {1: "up", 2: "down", 3: "testing", 4: "unknown", 5: "dormant",
6: "not present", 7: "lower layer down"},
"ups_battery": {1: "unknown", 2: "normal", 3: "low", 4: "depleted"},
}
# The units a custom line may name, with how each one reads, for the form's hint.
UNITS = {
"number": "a plain number",
"percent": "0 to 100",
"celsius": "degrees Celsius",
"volts": "volts",
"decivolts": "tenths of a volt",
"seconds": "a span in seconds",
"minutes": "a span in minutes",
"centiseconds": "a span in hundredths of a second (sysUpTime)",
"bytes": "a size in bytes",
"kilobytes": "a size in KiB",
"octets": "a byte counter, shown as traffic (bit/s)",
"count": "any other counter, shown per second",
}
_UPTIME = Reading("1.3.6.1.2.1.1.3.0", "uptime", "Uptime", "centiseconds")
# id: (label, what it is for, readings). Interface traffic is per interface
# and built by interface_readings from the numbers on the form.
PRESETS: dict[str, tuple[str, str, tuple[Reading, ...]]] = {
"system": ("System", "How long the device has been up. Nearly every SNMP device answers it.",
(_UPTIME,)),
"ups": ("UPS", "Battery state, charge, runtime left, load and input voltage (UPS-MIB, RFC 1628; "
"APC, Eaton and CyberPower management cards).",
(Reading("1.3.6.1.2.1.33.1.2.1.0", "battery_status", "Battery", "ups_battery"),
Reading("1.3.6.1.2.1.33.1.2.4.0", "battery_charge", "Charge", "percent"),
Reading("1.3.6.1.2.1.33.1.2.3.0", "runtime_left", "Runtime left", "minutes"),
Reading("1.3.6.1.2.1.33.1.4.4.1.5.1", "load", "Load", "percent"),
Reading("1.3.6.1.2.1.33.1.3.3.1.3.1", "input_voltage", "Input", "volts"),
Reading("1.3.6.1.2.1.33.1.2.2.0", "on_battery_for", "On battery", "battery_seconds"))),
"linux": ("Linux server", "CPU, memory and load from net-snmp (snmpd's UCD-SNMP-MIB).",
(Reading("1.3.6.1.4.1.2021.11.11.0", "cpu_used", "CPU used", "percent", scale=-1.0, offset=100.0),
Reading("1.3.6.1.4.1.2021.10.1.5.1", "load_1m", "Load (1m)", "number", scale=0.01),
Reading("1.3.6.1.4.1.2021.4.6.0", "memory_free", "Memory free", "kilobytes"),
Reading("1.3.6.1.4.1.2021.4.5.0", "memory_total", "Memory total", "kilobytes"))),
}
PRESET_ORDER = ("system", "interfaces", "ups", "linux")
INTERFACES_LABEL = ("Interface traffic", "Traffic in and out and link state for the interfaces numbered "
"below. Test the device to see its interfaces and their numbers.")
def parse_interfaces(text: str) -> list[int]:
"""'1, 2, 5-7' → [1, 2, 5, 6, 7]. Raises ValueError naming what it can't read."""
out: list[int] = []
for part in re.split(r"[,\s]+", (text or "").strip()):
if not part:
continue
m = re.fullmatch(r"(\d+)(?:-(\d+))?", part)
if not m:
raise ValueError(f"“{part}” is not an interface number or range")
lo, hi = int(m.group(1)), int(m.group(2) or m.group(1))
if hi < lo or hi - lo > 64:
raise ValueError(f"“{part}” is not a range of up to 64 interfaces")
out.extend(n for n in range(lo, hi + 1) if n not in out)
return out
def interface_readings(numbers: list[int], version: str) -> list[Reading]:
"""In, out and link state per interface. v2c and v3 read the 64-bit
counters (ifHCInOctets), which don't wrap on a fast link; v1 has only the
32-bit ones (ifInOctets)."""
hc = version != "1"
out: list[Reading] = []
for n in numbers:
rx = f"1.3.6.1.2.1.31.1.1.1.6.{n}" if hc else f"1.3.6.1.2.1.2.2.1.10.{n}"
tx = f"1.3.6.1.2.1.31.1.1.1.10.{n}" if hc else f"1.3.6.1.2.1.2.2.1.16.{n}"
out += [Reading(f"1.3.6.1.2.1.2.2.1.8.{n}", f"if{n}_status", f"Interface {n}", "if_status"),
Reading(rx, f"if{n}_in", f"Interface {n} in", "octets"),
Reading(tx, f"if{n}_out", f"Interface {n} out", "octets")]
return out
_OID = re.compile(r"\.?\d+(\.\d+)+")
_KEY = re.compile(r"[a-z][a-z0-9_]{0,63}")
def parse_custom(text: str) -> list[Reading]:
"""One reading a line: `OID name [unit]`. The name is a single word
(letters, digits, underscores) and becomes the metric name; the unit is
one of UNITS and defaults to number. Raises ValueError naming the line."""
out: list[Reading] = []
for i, raw in enumerate((text or "").splitlines(), start=1):
line = raw.split("#", 1)[0].strip()
if not line:
continue
parts = line.split()
if len(parts) not in (2, 3):
raise ValueError(f"Line {i}: write it as “OID name” or “OID name unit”")
oid, key = parts[0].lstrip("."), parts[1].lower()
unit = parts[2].lower() if len(parts) == 3 else "number"
if not _OID.fullmatch(oid):
raise ValueError(f"Line {i}: “{parts[0]}” is not an OID (numbers separated by dots)")
if not _KEY.fullmatch(key):
raise ValueError(f"Line {i}: the name “{parts[1]}” must start with a letter and use "
"only letters, digits and underscores")
if unit not in UNITS:
raise ValueError(f"Line {i}: “{parts[2]}” is not a unit; use one of {', '.join(UNITS)}")
out.append(Reading(oid, key, key.replace("_", " ").capitalize(), unit))
return out
def device_readings(presets: list[str], interfaces: list[int], custom: str, version: str) -> list[Reading]:
"""Every reading a device is asked for, presets in their order then custom
lines. Raises ValueError when two readings share a name."""
out: list[Reading] = []
for pid in PRESET_ORDER:
if pid == "interfaces":
if "interfaces" in presets:
out += interface_readings(interfaces, version)
elif pid in presets:
out += PRESETS[pid][2]
out += parse_custom(custom)
seen: set[str] = set()
for r in out:
if r.key in seen:
raise ValueError(f"Two readings are named “{r.key}”; give the custom one another name")
seen.add(r.key)
return out
def stored_unit(reading: Reading) -> str:
"""The unit a reading is stored in: a counter's rate unit, else its own."""
return COUNTER_UNITS[reading.unit][0] if reading.counter else reading.unit
def _bits(bps: float) -> str:
for unit, size in (("Gbit/s", 1e9), ("Mbit/s", 1e6), ("kbit/s", 1e3)):
if abs(bps) >= size:
return f"{bps / size:.3g} {unit}"
return f"{bps:.0f} bit/s"
def format_value(unit: str, value: float | None) -> str:
"""A stored value as a person reads it, in its unit."""
if value is None:
return "—"
if unit in STATUS_WORDS:
return STATUS_WORDS[unit].get(int(value), f"code {value:.0f}")
if unit == "centiseconds":
return human_duration(value / 100)
if unit == "seconds":
return human_duration(value)
if unit == "battery_seconds":
# UPS-MIB upsSecondsOnBattery: zero whenever the UPS is on mains power.
return f"for {human_duration(value)}" if value > 0 else "No, on mains"
if unit == "minutes":
return human_duration(value * 60)
if unit == "percent":
return f"{value:.0f}%"
if unit == "celsius":
return f"{value:.1f} °C"
if unit == "volts":
return f"{value:.0f} V"
if unit == "decivolts":
return f"{value / 10:.1f} V"
if unit == "bytes":
return human_bytes(value)
if unit == "kilobytes":
return human_bytes(value * 1024)
if unit == "bits_per_second":
return _bits(value)
if unit == "per_second":
return f"{value:.3g}/s"
return f"{value:,.0f}" if float(value).is_integer() else f"{value:.4g}"
# What a chart's axis says for a stored unit, and how its values scale for it.
def chart_axis(unit: str) -> tuple[str, float]:
return {"centiseconds": ("days", 1 / 8_640_000), "seconds": ("seconds", 1.0),
"battery_seconds": ("seconds on battery", 1.0),
"minutes": ("minutes", 1.0), "percent": ("%", 1.0), "celsius": ("°C", 1.0),
"volts": ("V", 1.0), "decivolts": ("V", 0.1), "bytes": ("MiB", 1 / 1_048_576),
"kilobytes": ("MiB", 1 / 1024), "bits_per_second": ("Mbit/s", 1e-6),
"per_second": ("per second", 1.0)}.get(unit, ("", 1.0))